About this product

The C&S Electric MRI1 is a numerical directional overcurrent and earth-fault relay from the High-Tech MR range. On a radial feeder, plain overcurrent grading is enough. On a ring, a parallel feeder or a meshed network, fault current can arrive from either end, and a non-directional relay will trip the healthy circuit as readily as the faulted one. The MRI1 adds a direction decision to the current measurement so that only the relay looking into the fault operates.

Documents

Datasheet

C&S Electric - MRI1-IE - Non-Directional 3 O/C + E/F Relay

Catalogue No:

MRI1-IE

C&S Electric

₹39,050/ nosexcl. GST₹46,079 incl. 18% GST2 nos in stock
SKYC005Basic Current Protection Relay1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price includes GST

Last updated:

Product Details

FieldValue
Product NameNon-Directional 3 O/C + E/F Relay
BrandC&S Electric
Catalogue / Part NumberMRI1-IE
SKUSKYC005
Product TypeBasic Current Protection Relay
MRP (excl. GST)₹39,050
Selling Price (excl. GST)₹39,050
Price incl. GST₹46,079
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
Input1A or 5A
OutputUp to 5 (trip 2 change-over; alarms 1 change-over each)
ParametersHighset, RS 485 communication option, display with keypad
ANSI Codes50, 51, 50N, 51N, 67, 67N, 50BF
Standards ComplianceIEC 60255-4 / BS 142 inverse characteristics; GL and Bureau Veritas approved
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
RangeI> 0.2-4.0 x In; I>> 1-40 x In; tI> 0.03-260 s definite time; IE> 0.01-2.0 x In; IE>> 0.01-15 x In; CBFP 0.1-2 s
Supply
  • Code L: 24 V (16-60 V AC / 16-80 V DC)
  • Code H: 110 V (50-270 V AC / 70-360 V DC)
Breaking Capacity250 x In dynamic; 100 x In for 1 s; 30 x In for 10 s; 4 x In continuous; VT 1.5 x UN continuous
Price List Specification
Key Features
Applications
Technical Specs
Protection Functions

Frequently Asked Questions for C&S Electric MRI1-IE Protection Relay

What are the key features of the C&S Electric MRI1-IE relay?

The key features of the C&S Electric MRI1-IE are: Phase and earth directional decision with selectable relay characteristic angle in seven steps; Earth-fault direction configurable for solid, resistance earthed, isolated or compensated systems; Withdrawable modules with automatic CT short-circuiting - safe removal under load; Transient overreach below 5% and dropout ratio above 97%; Inverse curves to IEC 255-4 / BS 142 plus definite time; Germanischer Lloyd and Bureau Veritas approved for marine use.

Why choose the C&S Electric MRI1-IE relay?

Choose the C&S Electric MRI1-IE when your circuit needs non-directional 3 O/C + E/F (phase overcurrent and earth fault) protection. Check the settings range and output contacts in the C&S Electric datasheet against your protection scheme before ordering.

Where is the C&S Electric MRI1-IE relay used?

The C&S Electric MRI1-IE is used for: MV feeder protection on doubly-fed lines and meshed systems; Back-up protection for distance and differential schemes; Ring main and parallel-feeder discrimination; Industrial and utility distribution substations; Marine and offshore power systems.

What CT and PT inputs are needed for the C&S Electric MRI1-IE relay?

Protection relays normally take 1A or 5A CT secondary inputs, and voltage-based functions need a PT secondary input. The exact input rating and burden depend on the model, so confirm them in the C&S Electric MRI1-IE datasheet. Use protection class CTs with enough VA burden for the relay and leads.

What is the difference between numerical, static and electromechanical protection relays?

Electromechanical relays operate with moving parts and offer limited adjustment. Static relays use analog electronics, usually for one protection function. Numerical relays are microprocessor-based, combine several protection functions in one unit, and usually add communication and event recording.

What are the technical specifications of the C&S Electric MRI1-IE relay?

The C&S Electric MRI1-IE technical specifications are: Technology: Microprocessor-based numerical relay with front display, digital (Fourier) filtering and self-supervision watchdog output relay; Auxiliary supply: Code L: 24 V (16-60 V AC / 16-80 V DC); Code H: 110 V (50-270 V AC / 70-360 V DC); Communication: RS485 serial interface, optional (order code R); slave address 1-32; Housing: 12TE; code A = 19 inch rack, code D = flush mounting; Inputs / outputs: Blocking input (aux voltage on D8/E8); electrical reset input (aux voltage on C8/D8); Installation: Installation depth 275 mm; leave 50 mm between units mounted one above another as the front cover opens downwards; Measuring inputs: 3 x CT 1 A / 5 A plus earth CT; VT 100 / 230 / 400 V; Rated frequency: 50 / 60 Hz adjustable; Setting ranges: I> 0.2-4.0 x In; I>> 1-40 x In; tI> 0.03-260 s definite time; IE> 0.01-2.0 x In; IE>> 0.01-15 x In; CBFP 0.1-2 s; Characteristics: Definite time or inverse time - Normal, Very and Extremely Inverse per IEC 255-4 / BS 142; Directional: Phase RCA 15/27/38/49/61/72/83 degrees in 7 steps. Earth: SR 110 deg / 170 deg for solid or resistance earthed systems, or ER for isolated / compensated systems; Output relays: Up to 5 (trip 2 change-over; alarms 1 change-over each); Burden: CT 0.2 VA at 1 A / 0.1 VA at 5 A; VT < 1 VA; Thermal rating: 250 x In dynamic; 100 x In for 1 s; 30 x In for 10 s; 4 x In continuous; VT 1.5 x UN continuous; Timing: Returning time 30 ms; minimum operating time 30 ms; time lag error +/- 10 ms; Other: Dropout ratio > 97%; transient overreach < 5%; Mechanical: Withdrawable modules with automatic CT short-circuiting; Ordering code: MRI1-(phase)(earth)-(aux)(RS485)(housing).

What protection functions does the C&S Electric MRI1-IE relay provide?

The C&S Electric MRI1-IE provides: Directional and non-directional phase overcurrent (I>, I>>), directional and non-directional earth fault (IE>, IE>>), phase and earth directional decision, circuit breaker failure protection.

Tags

  • MRI1-IE
  • MRI1-IE C&S Electric
  • Non-Directional 3 O/C + E/F Relay C&S Electric
  • Non-Directional 3 O/C + E/F Relay
  • C&S Electric Protection Relay
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?