The C&S Electric MRF2 is a numerical multi-stage frequency relay with rate-of-change-of-frequency measurement. System frequency is the most direct indicator of whether generation matches load: when load exceeds generation the frequency falls, and if nothing sheds load it keeps falling until the whole network collapses. A staged under-frequency scheme disconnects non-essential load in steps to arrest that decline.

Documents

Datasheet

C&S Electric - MRF2 - Numeric Multistage Frequency Relay

Catalogue No:

MRF2

C&S Electric

₹70,000/ nosexcl. GST₹82,600 incl. 18% GST2 nos in stock
SKYC061Frequency Protection Relay1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price includes GST

Last updated:

Product Details

FieldValue
Product NameNumeric Multistage Frequency Relay
BrandC&S Electric
Catalogue / Part NumberMRF2
SKUSKYC061
Product TypeFrequency Protection Relay
MRP (excl. GST)₹70,000
Selling Price (excl. GST)₹70,000
Price incl. GST₹82,600
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
InputVT 100 / 230 / 400 V
Output5 (R1-R2 with 2 change-over; R3-R4 with 1 change-over; R5 self-supervision)
Range30-70 Hz (fN 50 Hz) or 40-80 Hz (fN 60 Hz), in 0.01 Hz steps
Breaking Capacity0.05-2.0 x UN
Standards ComplianceIEC 60255 series
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
ParametersProgrammable under/over frequency and DF/DT, RS-485 communication, Flush Mounting, Drawout, Fault memory
Supply
  • Code L: 24 V (16-60 V AC / 16-80 V DC)
  • Code H: 110 V (50-270 V AC / 70-360 V DC)
Price List Specification
Key Features
Applications
Technical Specs
ANSI Codes81U (under frequency), 81O (over frequency), 81R (rate of change of frequency, df/dt)
Protection FunctionsFour independently settable frequency elements f1 to f4, each under or over frequency with its own delay, plus two rate-of-change-of-frequency (df/dt) elements

Frequently Asked Questions for C&S Electric MRF2 Protection Relay

What are the key features of the C&S Electric MRF2 relay?

The key features of the C&S Electric MRF2 are: Four independent frequency stages, each settable as under or over frequency with its own delay; Resolution of 0.01 Hz across a 30-70 Hz setting range; Two rate-of-change-of-frequency elements from 0.2 to 10 Hz/s for fast load shedding; Selectable df/dt measuring window from 2 to 64 periods trades speed against stability; Programmable assignment of elements to five output relays; Operating range from 0.05 to 2.0 x UN.

Why choose the C&S Electric MRF2 relay?

Choose the C&S Electric MRF2 when your circuit needs frequency protection. Check the settings range and output contacts in the C&S Electric datasheet against your protection scheme before ordering.

Where is the C&S Electric MRF2 relay used?

The C&S Electric MRF2 is used for: Multi-stage automatic under-frequency load shedding; Mains decoupling of captive generation on grid failure; Generator over- and under-frequency protection; Islanding detection in co-generation and embedded generation plants; Industrial networks that must shed load before the grid collapses.

What is the difference between numerical, static and electromechanical protection relays?

Electromechanical relays operate with moving parts and offer limited adjustment. Static relays use analog electronics, usually for one protection function. Numerical relays are microprocessor-based, combine several protection functions in one unit, and usually add communication and event recording.

What are the technical specifications of the C&S Electric MRF2 relay?

The C&S Electric MRF2 technical specifications are: Technology: Microprocessor-based numerical relay with front display, digital (Fourier) filtering and self-supervision watchdog output relay; Auxiliary supply: Code L: 24 V (16-60 V AC / 16-80 V DC); Code H: 110 V (50-270 V AC / 70-360 V DC); Communication: RS485 serial interface, optional (order code R); slave address 1-32; Housing: 12TE; code A = 19 inch rack, code D = flush mounting; Inputs / outputs: Blocking input (aux voltage on D8/E8); electrical reset input (aux voltage on C8/D8); Installation: Installation depth 275 mm; leave 50 mm between units mounted one above another as the front cover opens downwards; Measuring inputs: VT 100 / 230 / 400 V; Rated frequency: 50 / 60 Hz; Frequency setting range: 30-70 Hz (fN 50 Hz) or 40-80 Hz (fN 60 Hz), in 0.01 Hz steps; Time delay: tf up to 120 s; df/dt setting: +/- 0.2 to 10 Hz/s; measuring window 2 to 64 periods; Operating range: 0.05-2.0 x UN; Output relays: 5 (R1-R2 with 2 change-over; R3-R4 with 1 change-over; R5 self-supervision); Burden: < 1 VA at UN; Thermal rating: 2 x UN continuous; Timing: Dropout time 30 ms; minimum operating time 60 ms; time lag error +/- 10 ms; Dropout ratio: f> greater than 99.99% / f< less than 100.02%; Ordering code: MRF2-(voltage)(aux)(RS485)(housing).

What protection functions does the C&S Electric MRF2 relay provide?

The C&S Electric MRF2 provides: Four independently settable frequency elements f1 to f4, each under or over frequency with its own delay, plus two rate-of-change-of-frequency (df/dt) elements.

Which ANSI device codes does the C&S Electric MRF2 relay cover?

The C&S Electric MRF2 covers ANSI device codes 81U (under frequency), 81O (over frequency), 81R (rate of change of frequency, df/dt).

Tags

  • MRF2
  • MRF2 C&S Electric
  • Numeric Multistage Frequency Relay C&S Electric
  • Numeric Multistage Frequency Relay
  • C&S Electric Protection Relay
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?