C&S Electric - CSDPR-V2-400 - Self Powered O/C+E/F Relay with Drawout

C&S Electric - CSDPR-V2-400 - Self Powered O/C+E/F Relay with Drawout

About this product

The C&S Electric CSDPR-V2 is a self-powered overcurrent and earth-fault relay for ring main units and secondary distribution switchgear. The defining constraint in an RMU is that there is usually no station battery - no auxiliary DC supply at all. A conventional numerical relay simply cannot be used. The CSDPR-V2 draws the energy it needs to measure, decide and trip from the line current transformers themselves.

Documents

Datasheet

C&S Electric - CSDPR-V2-400 - Self Powered O/C+E/F Relay with Drawout

Catalogue No:

CSDPR-V2-400

C&S Electric

Request for Quote (RFQ)2 nos in stock
SKYC018Self Powered Relay - RMU1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price excludes GST

Last updated:

Product Details

FieldValue
Product NameSelf Powered O/C+E/F Relay with Drawout
BrandC&S Electric
Catalogue / Part NumberCSDPR-V2-400
SKUSKYC018
Product TypeSelf Powered Relay - RMU
MRP (excl. GST)-
Selling Price (excl. GST)-
Price incl. GST-
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
RangeDEFT, EINV, VINV, NINV3.0, NINV1.3, LINV, RI, HV-FUSE
ANSI Codes50P/51P, 50P, 50N/51N, 50N, 46, 62CLD, 50H, 50BF, SOTF, 74TC
Standards ComplianceIEC 60255 series; designed for RMU and secondary distribution service
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
InputSelf powered from the line current transformers; CT ratio 1 to 2500 for primary current display; frequency 50 / 60 Hz
Output2 latch type, plus 2 additional digital outputs when auxiliary supply is available
ParametersWide setting ranges for compact Ring main units with drawout, Flush Mounting, Front USB, Rear RS 485
SupplySelf powered - takes its operating energy from the line CTs, so no station battery or auxiliary supply is needed
Breaking CapacityTrip output 24 V @ 0.2 Ws pulse for series trip and 24 V @ 0.02 Ws pulse for flag; 2 latch-type digital outputs plus 2 more with auxiliary supply
Price List Specification
Key Features
Applications
Technical Specs
Protection Functions

Frequently Asked Questions for C&S Electric CSDPR-V2-400 Self Powered Relay - RMU

What are the key features of the C&S Electric CSDPR-V2-400 Self Powered Relay - RMU?

The key features of the C&S Electric CSDPR-V2-400 are: Self powered from the line CTs - protection works even with the station battery dead or absent; Two-stage phase and earth protection with eight selectable curves including RI and HV-FUSE; Front USB port works with an external power bank, so settings and records can be read on a de-energised RMU; Rear RS-485 with Modbus and IEC 60870-5-103 for SCADA integration; Cold load protection and inrush blocking prevent nuisance trips on energisation; Fault and event records with date and time stamp; Low-energy 24 V pulse trip output suited to RMU series trip coils.

Where is the C&S Electric CSDPR-V2-400 Self Powered Relay - RMU used?

The C&S Electric CSDPR-V2-400 is used for: Ring main unit (RMU) and compact substation protection; Secondary MV distribution networks; Package substations and pad-mounted switchgear; Distribution feeders where no auxiliary DC supply is available; Utility and industrial MV rings.

What is the C&S Electric CSDPR-V2-400 Self Powered Relay - RMU?

The C&S Electric CSDPR-V2-400 is the Self Powered O/C+E/F Relay with Drawout. Self Powered O/C+E/F Relay with Drawout (CSDPR-V2-400) from C&S Electric.

What are the technical specifications of the C&S Electric CSDPR-V2-400 Self Powered Relay - RMU?

The C&S Electric CSDPR-V2-400 technical specifications are: Technology: Self powered - takes its operating energy from the line CTs, so no station battery or auxiliary supply is needed; Phase characteristics: DEFT, EINV, VINV, NINV3.0, NINV1.3, LINV, RI, HV-FUSE; Earth characteristics: DEFT, EINV, VINV, NINV3.0, NINV1.3, LINV, RI, HV-FUSE; 1st stage phase pickup I>: 0.10 to 2.5 x IN (0.20 x IN minimum on the 200 series); DEFT trip time t>: 0.1 s to 150 s; Inverse TMS ti>: 0.01 to 1.500; 2nd stage phase short circuit I>>: 0.5 to 30 x IN; trip time t>> 0.00/0.03 s to 20 s; Earth fault 1st stage Ie>: 0.05 to 2.5 x IN; DEFT trip time te> 0.05 s to 150 s; TMS tie> 0.01 to 1.500; Earth fault 2nd stage Ie>>: 0.5 to 15 x IN; trip time te>> 0.04 s to 20 s; Phase unbalance: Pickup 5% to 80%; trip time tUnb 0.1 s to 150 s; CBFP: Enable yes/no; tCBFP 0.05 s to 2.0 s; Cold load protection: Disable / Enable; cold load active time tCdLd 0.1 s to 20 s; CT ratio: 1 to 2500 for primary current display; Frequency: 50 / 60 Hz; Trip output: One 24 V @ 0.2 Ws pulse output for series trip; one 24 V @ 0.02 Ws pulse output for flag; Digital outputs: 2 latch type, plus 2 additional digital outputs when auxiliary supply is available; Digital inputs: 2 or 3 for remote reset / remote trip / TCS; Communication: Front USB for PC or laptop interface (can connect an external power bank for display); rear RS-485; Protocol: Modbus and IEC 60870-5-103.

What protection functions does the C&S Electric CSDPR-V2-400 Self Powered Relay - RMU provide?

The C&S Electric CSDPR-V2-400 provides: Over current (I>), short circuit (I>>), earth fault (Ie>), earth high set (Ie>>), phase unbalance, cold load protection, inrush blocking on phase and earth, circuit breaker failure, switch on to fault, trip circuit supervision.

Which ANSI device codes does the C&S Electric CSDPR-V2-400 Self Powered Relay - RMU cover?

The C&S Electric CSDPR-V2-400 covers ANSI device codes 50P/51P, 50P, 50N/51N, 50N, 46, 62CLD, 50H, 50BF, SOTF, 74TC.

Which standards does the C&S Electric CSDPR-V2-400 Self Powered Relay - RMU comply with?

Standards and compliance for the C&S Electric CSDPR-V2-400: IEC 60255 series; designed for RMU and secondary distribution service.

Tags

  • CSDPR-V2-400
  • CSDPR-V2-400 C&S Electric
  • Self Powered O/C+E/F Relay with Drawout C&S Electric
  • Self Powered O/C+E/F Relay with Drawout
  • C&S Electric Self Powered Relay - RMU
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?