MCCB dsine DZ2 - 16 A, 4 Pole, 50 kA, Thermal-Magnetic Release

About this product
Lauritz Knudsen dsine DZ moulded case circuit breakers with thermal-magnetic release cover 16 A to 800 A in 3 pole and 4 pole versions across the DZ1, DZ2, DZ4, DZ6 and DZ7 frames at 36 kA, 50 kA and 80 kA breaking capacity, with 120 kA and 200 kA available on request. The overload setting is adjustable from 0.67 to 1.0 x In and the short-circuit setting from 6 to 12 x In. Features a transparent sealable release cover and ambient temperature compensation, and is available in fixed, plug-in, drawout, rotary and motorised versions. Ics equals 100 percent of Icu. Spreader terminals are included. Conforms to IS/IEC 60947-2.
Lauritz Knudsen
DZ2F0016NXC1AOOOOSpecifications
Purchase information
HSN 85362000 · GST 18% · price excludes GST
Product Details
| Field | Value |
|---|---|
| Product Name | MCCB dsine DZ2 - 16 A, 4 Pole, 50 kA, Thermal-Magnetic Release |
| Brand | Lauritz Knudsen |
| Catalogue / Part Number | DZ2F0016NXC1AOOOO |
| SKU | SKYLK566 |
| Product Type | MCCB (Thermal-Magnetic Release) |
| Description | Moulded case circuit breaker, dsine DZ2 frame, type designation DZ2-160N, rated 16 A, 4 Pole, breaking capacity Icu 50 kA at 415 V AC 50 Hz. Overload release range 11-16 A. Overload setting adjustable 0.67 - 1.0 x In, short-circuit setting adjustable 6 - 12 x In. Ics = 100 percent of Icu. For DZ1 and DZ2 16 A to 50 A the magnetic setting is fixed at 375 A. Spreader terminals included; phase barriers supplied. Standard packing 1 no. Catalogue number DZ2F0016NXC1AOOOO. Conforms to IS/IEC 60947-2. |
| MRP | ₹36,300 |
| Selling Price | ₹36,300 |
| Discount | - |
| GST Rate | 18% |
| HSN Code | 85362000 |
| Currency | INR |
| Availability | In Stock |
| Quantity Available | 5 nos |
| Field | Value |
|---|---|
| Min Order Quantity | 1 nos |
| Location | Bommanahalli |
| Input | 415 V AC 50 Hz |
| Output | - |
| Range | 16 A, overload release range 11-16 A |
| Parameters | 4 Pole, dsine DZ2 frame, type designation DZ2-160N, overload setting adjustable 0.67 - 1.0 x In, short-circuit setting adjustable 6 - 12 x In |
| Supply | - |
| Breaking Capacity | Icu 50 kA at 415 V AC 50 Hz, Ics = 100 percent of Icu |
| Price List Specification | - |
| Weight | 3.3 kg |
| Volumetric Weight | 1.482 kg |
| Dimensions (L × W × H) | 26 × 19 × 15 cm |
| Datasheet | - |
| Drawing / CAD | - |
The Lauritz Knudsen DZ2F0016NXC1AOOOO is a 4-pole moulded case circuit breaker rated at 16A with 50kA breaking capacity. It is fitted with a thermal-magnetic release for overload and short-circuit protection and belongs to the dsine DZ2 frame. It is used for protection of LT distribution circuits in industrial and commercial installations.
Choose the Lauritz Knudsen DZ2F0016NXC1AOOOO when your circuit needs 16A protection and the prospective fault current at the point of installation is within 50kA. It gives overload and short-circuit protection in one device. Accessories for remote tripping, status indication and operation differ by frame, so confirm the accessory list for this frame in the Lauritz Knudsen catalogue.
MCCBs of this rating are used to protect small feeders, motor circuits and control or auxiliary circuits where the fault level is higher than an MCB can break, for loads up to 16A.
MCCBs of this type are commonly fitted with a shunt release for remote tripping, an undervoltage release, auxiliary and alarm contacts for status signalling, a motor operator for remote switching, rotary handles for door-mounted operation, extended or spreader terminals, and padlocking devices. Availability depends on the frame size, so check the Lauritz Knudsen accessory list for the DZ2F0016NXC1AOOOO before ordering.
A thermal magnetic release uses a bimetal for overload and an electromagnet for short-circuit protection. It is simple and cost-effective for standard feeders. An electronic or microprocessor release measures current electronically and offers adjustable overload, short-circuit and, on some versions, earth fault settings. It is preferred where finer coordination between breakers is needed. Lauritz Knudsen names its microprocessor releases MTX on dsine DN breakers and iTRP on dsine DZ breakers.
Calculate the prospective short-circuit current at the point of installation from the transformer kVA and percentage impedance (plus the upstream fault level), reduced by the cable impedance in between, then select an MCCB whose breaking capacity (Icu) at your system voltage (415V) is at least that value. Where supply must continue after a fault, check the service breaking capacity (Ics) too. Breaking capacity versions differ by brand and frame size, so always read the kA value for the exact model. In the Lauritz Knudsen dsine DN and DZ ranges the letter in the type designation shows the Icu at 415V AC: C = 25kA, D = 36kA, N = 50kA, S = 70kA, H = 80kA. Other Lauritz Knudsen MCCB ranges use the letters differently, so always read the kA value stated for the exact model.
Yes, the Lauritz Knudsen DZ2F0016NXC1AOOOO (MCCB dsine DZ2 - 16 A, 4 Pole, 50 kA, Thermal-Magnetic Release) is listed on VendorStocks. Add it to your cart and choose “Continue to Buy”, or contact VendorStocks at +91 99021 83031 or support@skylightsenergy.in for a quotation, bulk quantities and delivery to your site in India.
You can buy the Lauritz Knudsen DZ2F0016NXC1AOOOO online on VendorStocks, the B2B electrical marketplace from Skylights Energy, Bangalore. The VendorStocks team can help with product selection.
Yes, VendorStocks takes bulk and project-quantity orders for the Lauritz Knudsen DZ2F0016NXC1AOOOO. Contact VendorStocks at +91 99021 83031 or support@skylightsenergy.in with your required quantity for a quotation on the full quantity and delivery to your site or panel manufacturing unit.
Yes. Contact VendorStocks at +91 99021 83031 or support@skylightsenergy.in with your quantity for a formal quotation on the Lauritz Knudsen DZ2F0016NXC1AOOOO, or add it to your cart and choose “Continue to Buy” to order directly. For a project with several items, email your BOM (Bill of Materials) to support@skylightsenergy.in for a single consolidated quote.
Yes, you can request the Lauritz Knudsen datasheet for the DZ2F0016NXC1AOOOO from VendorStocks at +91 99021 83031 or support@skylightsenergy.in.
Online payments on VendorStocks are processed securely through Razorpay. The payment options available for your order are shown at checkout.
Related Products

MCCB dsine DZ7 - 800 A, 3 Pole, 50 kA, Microprocessor Release iTRP1
₹1,45,400

MCCB dsine DU250 - 160 A, 3 Pole, 36 kA at 415 V AC, Thermal-Magnetic Release
₹13,800

MCCB dsine DN2 - 160 A, 4 Pole, 50 kA, Microprocessor Release MTX1.0
₹93,600

MCCB dsine DU400N - 400 A, 3 Pole, 50 kA at 415 V AC, Thermal-Magnetic Release
₹30,900

MCCB dsine DZ0 - 25 A, 3 Pole, 25 kA, Thermal-Magnetic Release
₹12,900

MCCB dsine DU100H - 20 A, 3 Pole, 30 kA at 415 V AC, Thermal-Magnetic Release
₹7,770
Related Categories · More from Lauritz Knudsen
Tags
Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.
Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.
Returns, replacements and warranty claims are handled by the seller under the manufacturer's warranty policy. See our Terms.
Your cart is empty
New Account
Create your account to continue
Already have an account?
Welcome back
Sign in to continue
Don't have an account?