C&S Electric - SY/SP - Static Check Synchronizing Relay

📦

About this product

The C&S Electric SY/SP is a static Synchronising Check Relay used to prevent wrong synchronisation of alternators during manual paralleling. Closing a generator breaker out of phase is one of the most destructive things that can happen in a power plant: the resulting current is limited only by machine reactance, and the mechanical shock can shear a coupling or damage the stator windings. The SY/SP sits between the operator and the breaker and simply refuses to permit a bad close.

Documents

Datasheet

C&S Electric - SY/SP - Static Check Synchronizing Relay

Catalogue No:

SY/SP

C&S Electric

₹55,000/ nosexcl. GST₹64,900 incl. 18% GST2 nos in stock
SKYC065Check/Auto Synchronizing Relay1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price includes GST

Last updated:

Product Details

FieldValue
Product NameStatic Check Synchronizing Relay
BrandC&S Electric
Catalogue / Part NumberSY/SP
SKUSKYC065
Product TypeCheck/Auto Synchronizing Relay
MRP (excl. GST)₹55,000
Selling Price (excl. GST)₹55,000
Price incl. GST₹64,900
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
RangeSelf-blocking potentiometers with screw for fine adjustment
ParametersFor Generators, Flush Mounting
Supply230 V or 110 V; permissible voltage limit +10 / -15%
ANSI Codes25 (synchronism / synchronism-check)
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
InputBus voltage on a-6, alternator voltage on b-7; galvanically isolated; phase-neutral or phase-phase connection possible
Output2 NO for switching in parallel; 2 NC for busbar voltage (dead bus); max 660 VA at 230 V AC
Breaking Capacity2 NO for switching in parallel; 2 NC for busbar voltage (dead bus); max 660 VA at 230 V AC
Price List Specification
Key Features
Applications
Technical Specs
Protection FunctionsSupervision of voltage difference, frequency difference and phase angle between busbar and incoming alternator; release of generator CB closing; dead-bus closing contact
Standards ComplianceC&S Functional Range; Germanischer Lloyd approved for marine use with frequency difference set no higher than 1 Hz

Frequently Asked Questions for C&S Electric SY/SP Check/Auto Synchronizing Relay

What are the key features of the C&S Electric SY/SP Check/Auto Synchronizing Relay?

The key features of the C&S Electric SY/SP are: Prevents out-of-phase paralleling by unskilled operators during manual synchronising; All three conditions - voltage difference, frequency difference and phase angle - checked before release; Separate dead-bus contact allows direct closing onto a de-energised busbar; Galvanically isolated inputs allow phase-neutral or phase-phase connection; Self-blocking potentiometers with fine screw adjustment hold their setting; No maintenance required, rated for 10^6 switching operations.

What is the C&S Electric SY/SP Check/Auto Synchronizing Relay?

The C&S Electric SY/SP is the Static Check Synchronizing Relay. Static Check Synchronizing Relay (SY/SP) from C&S Electric.

Where is the C&S Electric SY/SP Check/Auto Synchronizing Relay used?

The C&S Electric SY/SP is used for: Manual synchronising of alternators onto a live busbar; Check-synchronising permissive in generator control panels; Marine and offshore generating sets (Germanischer Lloyd approved); Diesel generating sets paralleled with the grid or with each other; Dead-bus closing of the first machine onto an un-energised board.

What are the technical specifications of the C&S Electric SY/SP Check/Auto Synchronizing Relay?

The C&S Electric SY/SP technical specifications are: Function: Monitors voltage difference, frequency difference and phase angle between bus and alternator; releases generator CB closing via contact 4-12 only when all are inside the set limits; Dead-bus closing: Separate contact 3-11, open when bus voltage is present on terminals a-6 and closed when the bus is dead; Measuring inputs: Bus voltage on a-6, alternator voltage on b-7; galvanically isolated; phase-neutral or phase-phase connection possible; Connection voltage: 230 V or 110 V; permissible voltage limit +10 / -15%; Nominal frequency: 50 / 60 Hz or 400 Hz; Frequency difference limit: 0.1-2 Hz adjustable (marine: max 1 Hz under Germanischer Lloyd); Voltage difference limit: 45-95 V AC adjustable; Settings: Self-blocking potentiometers with screw for fine adjustment; Consumption / duty: Approx. 3 VA; 100% ED continuous; Contacts: 2 NO for switching in parallel; 2 NC for busbar voltage (dead bus); max 660 VA at 230 V AC; Housing: CSPC standard case 141 x 105 x 91 mm (H x W x D); flush mounting; IP10 case, IP00 terminals; terminals M4 max 2.5 sq.mm; Weight: 0.4 kg; Service life: 10^6 switching operations; maintenance none; Limitation: Cannot supervise systems that are already synchronous (same voltage on a-6 and b-7) - it needs a beat between the systems; C&S recommends the PSY/N paralleling unit for that case; Ordering code: SY/SP-(110/230)-(50/400).

What protection functions does the C&S Electric SY/SP Check/Auto Synchronizing Relay provide?

The C&S Electric SY/SP provides: Supervision of voltage difference, frequency difference and phase angle between busbar and incoming alternator; release of generator CB closing; dead-bus closing contact.

Which ANSI device codes does the C&S Electric SY/SP Check/Auto Synchronizing Relay cover?

The C&S Electric SY/SP covers ANSI device codes 25 (synchronism / synchronism-check).

Which standards does the C&S Electric SY/SP Check/Auto Synchronizing Relay comply with?

Standards and compliance for the C&S Electric SY/SP: C&S Functional Range; Germanischer Lloyd approved for marine use with frequency difference set no higher than 1 Hz.

Tags

  • SY/SP
  • SY/SP C&S Electric
  • Static Check Synchronizing Relay C&S Electric
  • Static Check Synchronizing Relay
  • C&S Electric Check/Auto Synchronizing Relay
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?