About this product

The C&S Electric CSEZEN Series are top-of-range numerical IEDs for feeder, transformer and motor protection. This is the platform used where the substation is part of an automation scheme rather than a standalone panel: IEC 61850 Edition-2 communication, 1200 cycles of disturbance recording, configurable scheme logic and up to sixteen programmable digital inputs and outputs.

Documents

Datasheet

C&S Electric - CSEZEN-F-550-1-N-D-H - Advance Multifunction Feeder Relay F550 (1-N-D-H)

Catalogue No:

CSEZEN-F-550-1-N-D-H

C&S Electric

Request for Quote (RFQ)2 nos in stock
SKYC037Advance Current Protection Relay1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price excludes GST

Last updated:

Product Details

FieldValue
Product NameAdvance Multifunction Feeder Relay F550 (1-N-D-H)
BrandC&S Electric
Catalogue / Part NumberCSEZEN-F-550-1-N-D-H
SKUSKYC037
Product TypeAdvance Current Protection Relay
MRP (excl. GST)-
Selling Price (excl. GST)-
Price incl. GST-
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
Parameters1 element, N-D-H configuration, Drawout, Flush, optional IEC61850
SupplyL = 18-150 V DC, H = 80-280 V AC / 90-300 V DC, U = 40-280 V AC / 18-300 V DC
Standards ComplianceIEC 61850 (Edition-2), IEC 60870-5-103, MODBUS; IEC 60255 series
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
Input
  • F550/F600: 4 CT and 4 PT
  • M350: 4 CT and 3 PT
  • T200: 7 CT and 1 PT
  • F100/F300: 4 CT, F300 adds 4 PT
OutputUp to 16 user configurable digital outputs (8 on F100 / F300 / F100-U); MODBUS and IEC 60870-5-103 on RS-485 standard, IEC 61850 Edition-2 on RJ-45 on ordering
RangeProtection settings configured through the interactive HMI or the Designer suite M12 software; function set and setting ranges depend on model (F100, F300, F550, F600, M350, T200)
Breaking CapacityOutput relay contact ratings per the C&S CSEZEN catalogue - confirm against the ordering guide for the specific model
Price List Specification
Key Features
Applications
Technical Specs
ANSI Codes
Protection Functions

Frequently Asked Questions for C&S Electric CSEZEN-F-550-1-N-D-H Protection Relay

What are the key features of the C&S Electric CSEZEN-F-550-1-N-D-H relay?

The key features of the C&S Electric CSEZEN-F-550-1-N-D-H are: Draw-out construction with self CT shorting - the relay can be withdrawn from a live panel safely; IEC 61850 Edition-2 available on single or PRP dual-redundant RJ-45 ports for substation automation; 1200 cycles of disturbance recording for post-fault analysis; 20 fault records and 500 event records with date and time stamp; User configurable digital inputs and outputs, up to 16 of each; Selective relay scheme logic and blocking logic for interlocked schemes; Site-selectable 1 A / 5 A CT and 50 / 60 Hz, reducing the number of part numbers to stock; CT supervision and VT supervision prevent mal-operation on an instrument transformer failure.

Why choose the C&S Electric CSEZEN-F-550-1-N-D-H relay?

Choose the C&S Electric CSEZEN-F-550-1-N-D-H when your feeder circuit needs motor protection. Check the settings range and output contacts in the C&S Electric datasheet against your protection scheme before ordering.

Where is the C&S Electric CSEZEN-F-550-1-N-D-H relay used?

The C&S Electric CSEZEN-F-550-1-N-D-H is used for: MV and HV feeder protection in utility and industrial substations; Transformer protection with differential and restricted earth fault (T200); Large motor protection with locked rotor, stall and start supervision (M350); IEC 61850 based substation automation schemes; Incomer, bus-coupler and tie-breaker protection with check synchronising (F600); Generator and interconnector protection requiring power and frequency elements.

What CT and PT inputs are needed for the C&S Electric CSEZEN-F-550-1-N-D-H relay?

Protection relays normally take 1A or 5A CT secondary inputs, and voltage-based functions need a PT secondary input. The exact input rating and burden depend on the model, so confirm them in the C&S Electric CSEZEN-F-550-1-N-D-H datasheet. Use protection class CTs with enough VA burden for the relay and leads.

What is the difference between numerical, static and electromechanical protection relays?

Electromechanical relays operate with moving parts and offer limited adjustment. Static relays use analog electronics, usually for one protection function. Numerical relays are microprocessor-based, combine several protection functions in one unit, and usually add communication and event recording.

What are the technical specifications of the C&S Electric CSEZEN-F-550-1-N-D-H relay?

The C&S Electric CSEZEN-F-550-1-N-D-H technical specifications are: Technology: Numerical IED with draw-out relay and self CT shorting modular design; Rated CT: 1 A / 5 A site selectable (model dependent); Nominal frequency: 50 / 60 Hz site selectable; Analog inputs: F550/F600: 4 CT and 4 PT; M350: 4 CT and 3 PT; T200: 7 CT and 1 PT; F100/F300: 4 CT, F300 adds 4 PT; Digital input / output: Up to 16 DI / 16 DO on F550, F600, M350 and T200; 8 DI / 8 DO on F100, F300, F100-U; Fault records: 20 fault records with date and time stamp; Event records: 500 event records; Disturbance records: 1200 cycles of disturbance recording; Communication: MODBUS on RS-485 and IEC 60870-5-103 on RS-485 standard; IEC 61850 Edition-2 on single RJ-45 or PRP dual redundant RJ-45 on ordering; HMI: Interactive HMI with USB plug and play support; Configuration software: Common configuration Software - Designer suite M12; Auxiliary supply: L = 18-150 V DC, H = 80-280 V AC / 90-300 V DC, U = 40-280 V AC / 18-300 V DC; Overall dimensions: 190.5 (H) x 250.5 (W) x 231.5 (D) mm; Panel cut-out: 160 x 220 mm (F550/F600 class); 160 x 112 mm (F100/F300 class); Relay size F100/F300: 186.5 x 136.75 x 154.5 mm.

What protection functions does the C&S Electric CSEZEN-F-550-1-N-D-H relay provide?

The C&S Electric CSEZEN-F-550-1-N-D-H provides: Full multifunction feeder, transformer and motor protection: directional and non-directional over current and earth fault, voltage-controlled over current, voltage, frequency, power, thermal overload, breaker failure, broken conductor, auto-reclose, cold load pickup, harmonic blocking, CT and VT supervision.

Tags

  • CSEZEN-F-550-1-N-D-H
  • CSEZEN-F-550-1-N-D-H C&S Electric
  • Advance Multifunction Feeder Relay F550 (1-N-D-H) C&S Electric
  • Advance Multifunction Feeder Relay F550 (1-N-D-H)
  • C&S Electric Protection Relay
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?