C&S Electric - IRIProx-3ER - Static High Impedance Differential Relay

C&S Electric - IRIProx-3ER - Static High Impedance Differential Relay

About this product

The C&S Electric IRIProx-3ER is a static high impedance differential relay used chiefly for restricted earth fault protection of transformer and generator windings. Plain earth-fault protection has to be set above load and graded with downstream devices, which means it only covers the top part of a winding. Restricted earth fault, by contrast, compares the current entering and leaving a defined zone and can be set very sensitively, because in healthy operation the difference is zero by definition.

Documents

Datasheet

C&S Electric - IRIProx-3ER - Static High Impedance Differential Relay

Catalogue No:

IRIProx-3ER

C&S Electric

₹36,000/ nosexcl. GST₹42,480 incl. 18% GST2 nos in stock
SKYC073Transformer Protection Relay1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price includes GST

Last updated:

Product Details

FieldValue
Product NameStatic High Impedance Differential Relay
BrandC&S Electric
Catalogue / Part NumberIRIProx-3ER
SKUSKYC073
Product TypeTransformer Protection Relay
MRP (excl. GST)₹36,000
Selling Price (excl. GST)₹36,000
Price incl. GST₹42,480
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
Input1 A or 5 A
Output3 digital outputs
ParametersFlush Drawout, 3 nos Stabilizing resistors to be ordered separately
Supply18-300 V DC / 60-280 V AC
Breaking Capacity3 digital outputs; confirm contact ratings against the C&S IRIProx catalogue
ANSI Codes64R / 87G (restricted earth fault, high impedance differential)
Standards ComplianceIEC 60255 series
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
RangeRelay setting voltage calculated per application from CT knee-point voltage, CT secondary winding resistance, lead resistance and the required through-fault stability voltage
Price List Specification
Key Features
Applications
Technical Specs
Protection FunctionsHigh impedance restricted earth fault / differential protection using a stabilising resistor and non-linear resistor across the relay circuit

Frequently Asked Questions for C&S Electric IRIProx-3ER Protection Relay

What are the key features of the C&S Electric IRIProx-3ER relay?

The key features of the C&S Electric IRIProx-3ER are: High impedance principle gives extremely fast and sensitive earth-fault protection within the protected winding; Complete stability for through faults, even with heavy CT saturation on one CT; Covers a far higher proportion of the winding than plain earth-fault protection; Numeric measurement with true RMS and DFT filtering; Fault records with date and time stamp; Requires only one CT input plus the external stabilising resistor.

Why choose the C&S Electric IRIProx-3ER relay?

Choose the C&S Electric IRIProx-3ER for restricted earth fault (REF) protection of a transformer or generator winding zone. Check the settings range, stabilising resistor and output contacts in the C&S Electric datasheet against your protection scheme before ordering.

Where is the C&S Electric IRIProx-3ER relay used?

The C&S Electric IRIProx-3ER is used for: Restricted earth fault protection of transformer windings; Generator stator earth-fault protection; Busbar high impedance differential schemes; Reactor and earthing transformer protection; Any application needing sensitive earth-fault cover with through-fault stability.

What CT and PT inputs are needed for the C&S Electric IRIProx-3ER relay?

Protection relays normally take 1A or 5A CT secondary inputs, and voltage-based functions need a PT secondary input. The exact input rating and burden depend on the model, so confirm them in the C&S Electric IRIProx-3ER datasheet. Use protection class CTs with enough VA burden for the relay and leads.

What is the difference between numerical, static and electromechanical protection relays?

Electromechanical relays operate with moving parts and offer limited adjustment. Static relays use analog electronics, usually for one protection function. Numerical relays are microprocessor-based, combine several protection functions in one unit, and usually add communication and event recording.

What are the technical specifications of the C&S Electric IRIProx-3ER relay?

The C&S Electric IRIProx-3ER technical specifications are: Technology: Micro-controller based numeric design; measures true RMS with DFT filter; Analog inputs: Max 4 current analog inputs and max 4 voltage analog inputs (model dependent); Display: Bright 12 x 2 LCD with 3 front push buttons for HMI; Communication: Front USB communication for HMI; CSE LIVELINK configuration software; Auxiliary supply: 18-300 V DC / 60-280 V AC; Digital outputs: 3 digital outputs; Dimensions: Horizontal model 76.2 (H) x 155 (W) x 134.0 (D) mm; vertical model 155.0 x 76.2 x 134.0 mm; Panel cut-out: Horizontal 139.0 x 70.0 mm; vertical 70.0 x 139.0 mm; Principle: High impedance circulating current scheme - the relay is a voltage-sensitive element across the CT paralleling point, series connected with a stabilising resistor; CT input: 1 CT input (differential circuit); Stabilising resistor: External FGRES stabilising resistor sized to the through-fault stability voltage of the scheme; Protected zone: The winding between the phase CTs and the neutral CT - a fault outside this zone produces no operating current; Fault records: 5 fault records with date and time stamp; Digital outputs: 3 digital outputs; Rated current: 1 A or 5 A; Note: The stabilising resistor value and the relay setting voltage must be calculated from CT knee-point voltage, CT secondary resistance and lead burden for each application.

What protection functions does the C&S Electric IRIProx-3ER relay provide?

The C&S Electric IRIProx-3ER provides: High impedance restricted earth fault / differential protection using a stabilising resistor and non-linear resistor across the relay circuit.

Tags

  • IRIProx-3ER
  • IRIProx-3ER C&S Electric
  • Static High Impedance Differential Relay C&S Electric
  • Static High Impedance Differential Relay
  • C&S Electric Protection Relay
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?