C&S Electric - MRI1-IU - Voltage Controlled Overcurrent Relay

C&S Electric - MRI1-IU - Voltage Controlled Overcurrent Relay

About this product

The C&S Electric MRI1-IU is a digital voltage-controlled overcurrent relay. It exists to solve a specific and awkward problem with alternators: the sustained short-circuit current of a generator decays, within seconds, to something close to its full-load current. Set an ordinary overcurrent relay high enough not to trip on load and it will never see a sustained fault; set it low enough to see the fault and it trips on every motor start.

Documents

Datasheet

C&S Electric - MRI1-IU - Voltage Controlled Overcurrent Relay

Catalogue No:

MRI1-IU

C&S Electric

₹39,050/ nosexcl. GST₹46,079 incl. 18% GST2 nos in stock
SKYC008Basic Current Protection Relay1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price includes GST

Last updated:

Product Details

FieldValue
Product NameVoltage Controlled Overcurrent Relay
BrandC&S Electric
Catalogue / Part NumberMRI1-IU
SKUSKYC008
Product TypeBasic Current Protection Relay
MRP (excl. GST)₹39,050
Selling Price (excl. GST)₹39,050
Price incl. GST₹46,079
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
Input3 x CT 1 A / 5 A; VT 100 / 230 / 400 V
Output5 (two with 2 change-over, two with 1 change-over, plus self-supervision)
Breaking Capacity250 x In dynamic; 100 x In for 1 s; 30 x In for 10 s; 4 x In continuous
ANSI Codes50, 51, 51V (voltage controlled / voltage restrained overcurrent)
Standards ComplianceIEC 60255-4 / BS 142 inverse characteristics
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
RangeISN / ISL 0.2-4.0 x In; tI> 0.03-260 s definite time or 0.05-10 inverse; I>>N / I>>L 1-40 x In; tI>> 0.03-2 s
ParametersFault records, LBB, programmable O/P Relays, remote reset, remote blocking, Flush, Drawout
Supply
  • Code L: 24 V (16-60 V AC / 16-80 V DC)
  • Code H: 110 V (50-270 V AC / 70-360 V DC)
Price List Specification
Key Features
Applications
Technical Specs
Protection FunctionsTwo-stage overcurrent (I> and I>>), each with a normal-voltage (N) and a low-voltage (L) pickup setting, switched by an undervoltage supervision element

Frequently Asked Questions for C&S Electric MRI1-IU Protection Relay

What are the key features of the C&S Electric MRI1-IU relay?

The key features of the C&S Electric MRI1-IU are: Separate normal-voltage and low-voltage pickup settings for both overcurrent stages; Automatic switch-over to the lower pickup when the undervoltage element detects a collapsed system voltage; Solves the classic problem of alternator fault current decaying below the overcurrent setting; Definite time plus Normal, Very and Extremely Inverse curves; Five output relays including a self-supervision watchdog; Withdrawable modules with automatic CT short-circuiting.

Why choose the C&S Electric MRI1-IU relay?

Choose the C&S Electric MRI1-IU when your circuit needs generator protection. Check the settings range and output contacts in the C&S Electric datasheet against your protection scheme before ordering.

Where is the C&S Electric MRI1-IU relay used?

The C&S Electric MRI1-IU is used for: Generator and alternator overcurrent back-up protection; Plants where generator fault current decays close to full-load current; Captive power generation and emergency generating sets; Transformer back-up protection on sources with limited fault level; Any system where fault level and load current are uncomfortably close.

What CT and PT inputs are needed for the C&S Electric MRI1-IU relay?

Protection relays normally take 1A or 5A CT secondary inputs, and voltage-based functions need a PT secondary input. The exact input rating and burden depend on the model, so confirm them in the C&S Electric MRI1-IU datasheet. Use protection class CTs with enough VA burden for the relay and leads.

What is the difference between numerical, static and electromechanical protection relays?

Electromechanical relays operate with moving parts and offer limited adjustment. Static relays use analog electronics, usually for one protection function. Numerical relays are microprocessor-based, combine several protection functions in one unit, and usually add communication and event recording.

What are the technical specifications of the C&S Electric MRI1-IU relay?

The C&S Electric MRI1-IU technical specifications are: Technology: Microprocessor-based numerical relay with front display, digital (Fourier) filtering and self-supervision watchdog output relay; Auxiliary supply: Code L: 24 V (16-60 V AC / 16-80 V DC); Code H: 110 V (50-270 V AC / 70-360 V DC); Communication: RS485 serial interface, optional (order code R); slave address 1-32; Housing: 12TE; code A = 19 inch rack, code D = flush mounting; Inputs / outputs: Blocking input (aux voltage on D8/E8); electrical reset input (aux voltage on C8/D8); Installation: Installation depth 275 mm; leave 50 mm between units mounted one above another as the front cover opens downwards; Measuring inputs: 3 x CT 1 A / 5 A; VT 100 / 230 / 400 V; Rated frequency: 50 / 60 Hz adjustable; Setting ranges: ISN / ISL 0.2-4.0 x In; tI> 0.03-260 s definite time or 0.05-10 inverse; I>>N / I>>L 1-40 x In; tI>> 0.03-2 s; Voltage setting: U 10-110 V (UN 100 V), 20-250 V (UN 230 V), 40-440 V (UN 400 V); Characteristics: Definite time or inverse time - Normal, Very and Extremely Inverse per IEC 255-4 / BS 142; Output relays: 5 (two with 2 change-over, two with 1 change-over, plus self-supervision); Burden: CT 0.2 VA at 1 A / 0.1 VA at 5 A; VT < 1 VA; Thermal rating: 250 x In dynamic; 100 x In for 1 s; 30 x In for 10 s; 4 x In continuous; Timing: Returning time 30 ms; minimum operating time 30 ms; time lag error +/- 10 ms; Other: Dropout ratio > 97%; 200 ms trip-contact dwell time; Ordering code: MRI1-(I1/I5)(U1/U2/U4)(housing).

What protection functions does the C&S Electric MRI1-IU relay provide?

The C&S Electric MRI1-IU provides: Two-stage overcurrent (I> and I>>), each with a normal-voltage (N) and a low-voltage (L) pickup setting, switched by an undervoltage supervision element.

Tags

  • MRI1-IU
  • MRI1-IU C&S Electric
  • Voltage Controlled Overcurrent Relay C&S Electric
  • Voltage Controlled Overcurrent Relay
  • C&S Electric Protection Relay
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?