C&S Electric - MRR1 - Numeric Rotor Earthfault Protection Relay

C&S Electric - MRR1 - Numeric Rotor Earthfault Protection Relay

About this product

The C&S Electric MRR1 is a multifunctional generator rotor protection relay combining rotor earth-fault protection, excitation over- and under-current protection and rotating diode failure detection. A single earth fault on a field winding does no immediate damage - which is precisely why it must be found. A second earth fault would short part of the field winding, unbalance the magnetic flux and cause severe mechanical damage to the machine.

Documents

Datasheet

C&S Electric - MRR1 - Numeric Rotor Earthfault Protection Relay

Catalogue No:

MRR1

C&S Electric

₹1,85,000/ nosexcl. GST₹2,18,300 incl. 18% GST2 nos in stock
SKYC064Generator & Power Protection Relay1 seller

Purchase information

Availability
In stock — 2 nos ready to ship
Minimum order
1 nos
Ships from
Bommanahalli · 560068
Delivery
Across India · shipping calculated at checkout from your pincode
  • 100% Genuine
  • Manufacturer Warranty
  • Secure Payments
  • Delivery Across India

HSN 85362010 · GST 18% · price includes GST

Last updated:

Product Details

FieldValue
Product NameNumeric Rotor Earthfault Protection Relay
BrandC&S Electric
Catalogue / Part NumberMRR1
SKUSKYC064
Product TypeGenerator & Power Protection Relay
MRP (excl. GST)₹1,85,000
Selling Price (excl. GST)₹1,85,000
Price incl. GST₹2,18,300
Discount-
GST Rate18%
HSN Code85362010
CurrencyINR
AvailabilityIn Stock
Quantity Available2 nos
Min Order Quantity1 nos
LocationBommanahalli
Input1 kOhm to 1 MOhm
Standards ComplianceIEC 60255 series
Weight-
Volumetric Weight-
Dimensions (L × W × H)-
DatasheetView datasheet
Drawing / CAD-
Description
Output5 (R1-R2 with 2 change-over; R3-R4 with 1 change-over; R5 self-supervision, normally energised)
RangeRW 20-200 kOhm; R< 2-20 kOhm; tRW and tR< 1-50 s; Ie< and Ie> 0.2-20 A; tIe 0.1-10 s; Ir 10-400%
ParametersDiode failure and under/over excitation protection for large Generators with RS 485 communication, Flush Mounting, Drawout
Supply
  • Code L: 24 V (16-60 V AC / 16-80 V DC)
  • Code H: 110 V (50-270 V AC / 70-360 V DC)
Breaking Capacity5 output relays - R1 and R2 with 2 change-over contacts each, R3 and R4 with 1 change-over each, R5 self-supervision normally energised
Price List Specification
Key Features
Applications
Technical Specs
ANSI Codes37 (DC undercurrent), 40 (field relay), 58 (rectification failure), 64 (ground detector), 76 (DC overcurrent)
Protection FunctionsTwo-stage rotor earth fault (warning RW and trip R<), exciter DC undercurrent (Ie<), exciter DC overcurrent (Ie>) and rotating diode failure by ripple detection (Ir)

Frequently Asked Questions for C&S Electric MRR1 Protection Relay

What are the key features of the C&S Electric MRR1 relay?

The key features of the C&S Electric MRR1 are: Detects high-impedance rotor earth faults using a 0.5 Hz test voltage, which avoids false measurement from rotor-to-earth capacitance up to 1 uF; Two-stage insulation supervision - one stage for warning, one for trip, with independent resistance and time settings; Live display of insulation resistance in kOhm and exciter current in amps; Rotating diode failure detection by measuring the ripple component of the excitation current; Hall-transducer current measurement, galvanically isolated, 0 to 20 A range; Short-circuit and overvoltage proof measuring input; Programmable blocking input and assignment of functions to output relays as alarm or trip.

Why choose the C&S Electric MRR1 relay?

Choose the C&S Electric MRR1 when your generator circuit needs earth fault protection. Check the settings range and output contacts in the C&S Electric datasheet against your protection scheme before ordering.

Where is the C&S Electric MRR1 relay used?

The C&S Electric MRR1 is used for: Rotor earth-fault protection of synchronous generators, brushed and brushless; Excitation system supervision on turbo and hydro generators; Rotating diode failure detection on brushless exciters; Field failure and over-excitation protection; Power station and captive generation protection panels.

What CT and PT inputs are needed for the C&S Electric MRR1 relay?

Protection relays normally take 1A or 5A CT secondary inputs, and voltage-based functions need a PT secondary input. The exact input rating and burden depend on the model, so confirm them in the C&S Electric MRR1 datasheet. Use protection class CTs with enough VA burden for the relay and leads.

What is the difference between numerical, static and electromechanical protection relays?

Electromechanical relays operate with moving parts and offer limited adjustment. Static relays use analog electronics, usually for one protection function. Numerical relays are microprocessor-based, combine several protection functions in one unit, and usually add communication and event recording.

What are the technical specifications of the C&S Electric MRR1 relay?

The C&S Electric MRR1 technical specifications are: Technology: Microprocessor-based numerical relay with front display, digital (Fourier) filtering and self-supervision watchdog output relay; Auxiliary supply: Code L: 24 V (16-60 V AC / 16-80 V DC); Code H: 110 V (50-270 V AC / 70-360 V DC); Communication: RS485 serial interface, optional (order code R); slave address 1-32; Housing: 12TE; code A = 19 inch rack, code D = flush mounting; Inputs / outputs: Blocking input (aux voltage on D8/E8); electrical reset input (aux voltage on C8/D8); Installation: Installation depth 275 mm; leave 50 mm between units mounted one above another as the front cover opens downwards; Insulation measurement: Low frequency alternating test voltage +/- 24 V at 0.5 Hz injected via slip rings to the main exciter winding and rotor earth; Measuring resistance range: 1 kOhm to 1 MOhm; Max input voltage: 600 V DC; Exciter DC current measurement: Galvanically isolated via Hall transducer; nominal current IN 10 A DC; measuring range 0 to 20 A; Power consumption in current circuit: < 1 VA; Setting ranges: RW 20-200 kOhm; R< 2-20 kOhm; tRW and tR< 1-50 s; Ie< and Ie> 0.2-20 A; tIe 0.1-10 s; Ir 10-400%; Default settings: RW 80.0 kOhm, tRW 1.00 s; R< 20.0 kOhm, tR< 1.00 s; Ie< 0.50 A, tIe< 0.10 s; Ie> 5.00 A, tIe> 0.1 s; Ir 50%, tIr 0.1 s; Accuracy: Insulation and current pickup +/- 5% of setting; trip delays +/- 3% or +/- 150 ms; Output relays: 5 (R1-R2 with 2 change-over; R3-R4 with 1 change-over; R5 self-supervision, normally energised); Timing: Returning time < 30 ms; minimum operating time < 100 ms; dropout to pickup ratio > 98%; Temperature influence: +/- 2.5% from -20 C to +70 C; Weight: Approx. 1.5 kg; Dimensions: 12TE case; cut-out 136.5 x 68.7 mm; installation depth 275 mm; Ordering code: MRR1-(aux L/H)(RS485 R)(housing A/D).

What protection functions does the C&S Electric MRR1 relay provide?

The C&S Electric MRR1 provides: Two-stage rotor earth fault (warning RW and trip R<), exciter DC undercurrent (Ie<), exciter DC overcurrent (Ie>) and rotating diode failure by ripple detection (Ir).

Tags

  • MRR1
  • MRR1 C&S Electric
  • Numeric Rotor Earthfault Protection Relay C&S Electric
  • Numeric Rotor Earthfault Protection Relay
  • C&S Electric Protection Relay
  • VendorStocks India

Payment, Delivery & Returns

Secure payments

Pay by UPI, card or net banking through a PCI-DSS compliant payment gateway (Razorpay). Card and UPI details are never stored on VendorStocks.

Delivery

Delivered anywhere in India, straight from the seller's warehouse. Shipping is calculated at checkout from your delivery pincode and the item's weight.

Returns & warranty

Returns, replacements and warranty claims are handled by the seller under the manufacturer's policy and dealership terms. See our Return & Refund Policy.

Cart

Your cart is empty

New Account

Create your account to continue

or

Already have an account?

Welcome back

Sign in to continue

or

Don't have an account?